West Control Solutions 8010+ 1/8 DIN Temperature/Process Indicator 24V Powered
24West 1/8 DIN Temperature & Process Indicator, Universal Input; Up to 5 outputs are available.
The ISE/ West 8010 Plus is a 1/8 DIN microprocessor based digital indicator, available with red, green or changeable red & green displays. Fixed red display is standard while other display colors could delay shipment by up to 2 weeks. Up to 5 outputs are available. The digital indicator can be reconfigured with available plug-in modules.
Four-digit LED display
Engineering units
Up to 5 alarms
PC configuration
Transmitter power supply option
PV retransmit option
Min/max value hold
RS485 comms option
Features
Output Configuration Up to 5 total., max 5 for Alarms, max 2 triac outputs, max 3 for retransmit of PV, max 1 transmitter power supply
Alarm 1- 5 Types Process high, process low, direct acting, process high, process low reverse and logical OR. Latching function is available on all alarms
Viewable Values Process variable, maximum value, minimum value and elapsed time since reset
Legends C/F LED.
Human Interface 3 button operation, 4 digit 13mm high red or green display, plus set-up, alarm, max & min indicators
PC Configuration Off-line configuration from serial port to dedicated configuration socket (comms option not required)
Input
Thermocouple - J, K, R, S, T, B, L, C, Pt-Rh20% vs Pt-Rh40% & N.
RTD - 3 Wire PT100, 50ohm per lead maximum (balanced).
DC Linear - 0-20/4-20mA, 0-50/10-50mV, 0-5/1-5/0-10/2-10V. Scaleable -1999 to 9999, decimal point selectable.
Impedance - >10Mohm for Thermocouple and mV ranges, 47Kohm for V ranges and 5ohm for mA ranges.
Accuracy - +/- 0.1% of input span +/- 1 LSD (T/C CJC better than 1C).
Sampling - 4 per second, 14 bit resolution.
Sensor Break Detection - <2 secs="" except="" zero="" based="" dc="" ranges="" control="" o="" p="" s="" turn="" off="" high="" alarms="" activate="" for="" t="" c="" and="" mv="" low="" rtd="" ma="" or="" v="" br="">
Outputs & Options
Single Relay Output Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations, latching or non-latching. (3 maximum in control)
Dual Relay Output Contacts SPST 2 Amp resistive at 240V AC,>200,000 operations. (May be fitted in output 2 or 3 only)
Retransmit Output 0-20/4-20mA into 500 ohm max, 0-10/0-5V into 500 ohm min. Accuracy: +/- 0.25%
Transmitter Power Supply 20-28V DC (24V nominal), min load 910 ohm
Digital Inputs External reset of latching alarm 1 relay. Volt free or TTL input (Reset = open to close or "0" to "1" transition. 0 = -0.6 to 0.8V, 1 = 2 to 24V); Can be used to reset latched alarms or set tare.
Communications
2 wire RS485, 1200 to 19200 baud. Modbus or West ASCII (selectable)
General
Temperature & RH 0 to 55C (-20 to 80C storage), 20% to 95%RH non-condensing
Power Supply 90 to 264V 50/60Hz (optional 20 to 55V AC/22 to 65V DC), approx 4 Watts
Front Panel Protection IEC IP66 (Behind panel protection is IP20)
Approvals and Certification CE, UL & ULc
Additional Information
- Input0-800F J T/C, 0.0-800.0F J T/C, 0.0-450.0C J T/C, 0-1600F J T/C, 0-1000C J T/C, 0-2500F K T/C, 0-1373C K T/C, -199.9 - 999.9F K T/C, -128.8 - 537.7C K T/C, -199.9 - 752.0F T T/C, -128.8 - 400.0C TK T/C, 0-450C J T/C, -400 - 752F T T/C, -240 - 400C T T/C, 32 -3198F R T/C, 0 - 1759C R T/C, 32 -3204F S T/C, 0 - 1762C S T/C, 211 - 3315F B T/C, 100 - 1824C B T/C, 32 - 2551F N T/C, 0 - 1399C N T/C, -328 - 1401F PT100 RTD, -128.8 - 537.7C PT100 RTD, 0 - 20 mA Linear, 4 - 20 mA Linear, 0 - 50 mVDC Linear, 10 - 50 mVDC Linear, 0 - 5 VDC Linear, 1 - 5 VDC Linear, 0 - 10 VDC Linear, -199.9-999.9F PT100 RTD, -199 to 800C PT100 RTD, 2 - 10 VDC Linear
- Output #1(0) None, (1) Relay, (2) SSR Drive, (8) Triac, (7) Linear 4-20mADC, (4) Linear 0-20mADC, (5) Linear 0-5VDC, (3) Linear 0-10VDC, (6) Linear 2-10VDC
- Output #2(0) None, (1) Relay (Low Process Alarm), (1) Relay (High Alarm), (9) Dual Relay, (7) Linear 4-20mA Retransmit, (4) Linear 0-20mADC Retransmit, (3) Linear 0-10VDC Retransmit, (5) Linear 0-5VDC Retransmit, (6) Linear 2-10VDC Retransmit, (2) SSR Drive (High Process Alarm), (2) SSR Drive (Low Process Alarm), (8) Triac (Low Process Alarm), (8) Triac (High Process Alarm)
- Output #3(0) None, (1) Relay (Low Process Alarm), (1) Relay (High Process Alarm), (9) Dual Relay, (7) Linear 4-20mADC Retransmit PV, (4) Linear 0-20mADC Retransmit PV, (5) Linear 0-5VDC Retransmit PV, (3) Linear 0-10VDC Retransmit PV, (8) Transmitter Power Supply
- Options(0) None, (1) RS485 Communications, (3) Digital Input (Remote Reset)
- Power Supply(2) 24 VAC/VDC Powered, Select
- Display Color(0) Red, Select
- ManufacturerWest
- EC44-0
- Power SupplySelect
- Agency Listing
- ULYes
- cULYes
- CEYes