1. How do I wire a 4 wire RTD to a 3 wire input on a control?
    You can connect a 4 wire RTD to a 3 wire instrument.  Just use 3 of the wires.  Generally
    glx25v Fri, 08/17/2018 - 17:29
  2. I cannot activate Self Tune. What is likely causing this?
    Self Tune cannot be activate if the primary or the secondary proportioning band is set to 0.
    glx25v Fri, 08/17/2018 - 17:29
  3. I cannot turn on Pre-Tune. What is likely causing this?
    Pre-tune cannot be activated if: 1) The setpoint is ramping.2) The process variable is less than 5%
    glx25v Fri, 08/17/2018 - 17:29
  4. I want to buy a 6100+, 8100+, or 4100+ control that is the same as one I already have. How do I find out what is in my existing control?
    If you are replacing or adding an additional P6100, P8100 or P4100 control:  ISE needs informat
    glx25v Fri, 08/17/2018 - 17:29
  5. How do I get a calibration procedure for the West 4700 (N series) limit controller?
    The calibration procedure can be found here:Calibration Procedure There is no provision for offset a
    glx25v Fri, 08/17/2018 - 17:29
  6. My upper display has all the decimal points lit on my (N Series control). How can I clear this problem?
    Acknowledging the 'Default' Display (6100/8100/4100 N Series) Note: parameters shown are for illustr
    glx25v Fri, 08/17/2018 - 17:29
  7. How do I change the input range of my 6100/8100/4100 (N Series) controller?
    To change the input range of the controller Note: parameters shown are for illustration purposes onl
    glx25v Fri, 08/17/2018 - 17:29
  8. What are the standard parameter settings for the 6100/8100/4100 (N Series)controls?
    Below are the common control parameters we recommend for (2) output controls. These are the settings
    glx25v Fri, 08/17/2018 - 17:29